Assessment Year 2001
Principal Product Fire suppressant systems
NAICS
n/a
SIC 3829: Measuring and Controlling Devices, Not Elsewhere Classified
Sales Range $50
M
to 100
M
# of Employees 320
Plant Area 85,000
ft2
Annual Production 793,250
pieces
Production Hrs. Annual 6,000
hrs
Location (State) North Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $171,760 5,204,850
kWh
Electricity Demand $188,771 9,400
kW-mo/yr
Electricity Fees $6,800 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $52,485 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $34,603

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings
01 2.1311: Replace electrically-operated equipment with fossil fuel equipment $14,086 $7,500 $12,672
384,000
kWh
$14,784
-
kW-mo/yr
$(-12,870.0)
-
MMBtu
$(-500.0)
02 2.3416: Use combined cycle gas turbine generator sets with waste heat boilers connected to turbine exhaust $16,136 $45,000 $3,036
92,000
kWh
$17,940
-
kW-mo/yr
$(-3,840.0)
-
MMBtu
$(-1,000.0)
03 2.2437: Recover waste heat from equipment $1,746 $5,000 $(-792.0)
(-24,000)
kWh
$(-924.0)
-
kW-mo/yr
$3,462
-
MMBtu
-
04 2.7241: Install outside air damper / economizer on hvac unit $19,065 $40,000 $16,620
503,644
kWh
$2,445
-
kW-mo/yr
- -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $1,339 $1,690 $618
18,720
kWh
$721
-
kW-mo/yr
- -
06 2.7228: Avoid introducing hot, humid, or dirty air into hvac system $113 $300 $52
1,573
kWh
$61
-
kW-mo/yr
- -
TOTAL RECOMMENDED $52,485 $99,490 $32,206
975,937
kWh
$35,027
-
kW-mo/yr
$(-13,248.0)
-
MMBtu
$(-1,500.0)
TOTAL IMPLEMENTED $34,603 $49,490 $29,962
907,937
kWh
$18,011
-
kW-mo/yr
$(-12,870.0)
-
MMBtu
$(-500.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs