Assessment Year | 1997 |
---|---|
Principal Product | Cotton and synthetic yarns |
NAICS |
n/a
|
SIC | 2281: Yarn Spinning Mills |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
250,000
ft2
|
Annual Production | 22,000,000
lb
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $635,047 | 18,285,463 |
kWh
|
$0.035 |
Electricity Demand | $460,575 | 40,940 |
kW-mo/yr
|
$11.25 |
Electricity Fees | $(-228,054.0) | - |
|
- |
Natural Gas | $10,288 | 1,908 |
MMBtu
|
$5.39 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $110,232 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Raw Material Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7124: Make a practice of turning off lights when not needed | $9,780 | - | n/a |
$6,378
63,013
kWh
|
$3,402
-
kW-mo/yr
|
- | - | - | - |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,183 | $397 | n/a |
$2,717
78,253
kWh
|
$1,466
-
kW-mo/yr
|
- | - | - | - |
03 | 2.2694: Use highest temperature for chilling or cold storage | $1,601 | $20 | n/a |
$987
28,429
kWh
|
$614
-
kW-mo/yr
|
- | - | - | - |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,698 | $300 | n/a |
$7,410
213,365
kWh
|
$3,288
-
kW-mo/yr
|
- | - | - | - |
05 | 3.5311: Recover and reuse waste material | $16,220 | $260 | n/a | - | - | $(-3,780.0) | - | $20,000 | - |
06 | 2.8114: Change rate schedules or other changes in utility service | $7,750 | $10,280 | n/a | - | - | - | - | - |
$7,750
-
Tgal
|
07 | 4.511: Expand operations into unused space | $60,000 | $1,080 | n/a | - | - | - | $60,000 | - | - |
TOTAL RECOMMENDED | $110,232 | $12,337 |
$17,492
383,060
kWh
|
$8,770
-
kW-mo/yr
|
$(-3,780.0) | $60,000 | $20,000 |
$7,750
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Raw Material Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs