| Assessment Year | 1995 |
|---|---|
| Principal Product | Custom Built Air Handlers |
| NAICS |
n/a
|
| SIC | 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment |
| Sales Range | $10 M to 50M |
| # of Employees | 125 |
| Plant Area |
188,000
ft2
|
| Annual Production | 300
pieces
|
| Production Hrs. Annual | 3,000
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $102,931 | 1,830,891 |
kWh
|
$0.056 |
| Natural Gas | $29,824 | 5,787 |
MMBtu
|
$5.15 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $10,327 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $7,597 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $518 | $210 |
$518
7,620
kWh
|
- | - | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $480 | $556 |
$480
7,034
kWh
|
- | - | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,041 | $1,134 |
$4,041
58,324
kWh
|
- | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,178 | $1,710 |
$1,178
13,775
kWh
|
- | - | - | |
| 05 | 2.7492: Use proper thickness of insulation on building envelope | $513 | $1,200 |
$135
2,052
kWh
|
$378
-
MMBtu
|
- | - | |
| 06 | 2.4322: Use or replace with energy efficient substitutes | $1,347 | $1,910 |
$1,347
8,206
kWh
|
- | - | - | |
| 07 | 3.4115: Recover and reuse cooling water | $2,250 | $3,500 |
$(-202.0)
2,931
kWh
|
- |
$2,502
-
Tgal
|
$(-50.0) | |
| TOTAL RECOMMENDED | $10,327 | $10,220 |
$7,497
99,942
kWh
|
$378
-
MMBtu
|
$2,502
-
Tgal
|
$(-50.0) | ||
| TOTAL IMPLEMENTED | $7,597 | $6,164 |
$7,219
89,977
kWh
|
$378
-
MMBtu
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs