| Assessment Year | 2013 |
|---|---|
| Principal Product | Asphalt |
| NAICS | 324121: Asphalt Paving Mixture and Block Manufacturing |
| SIC | 2951: Asphalt Paving Mixtures and Blocks |
| Sales Range | $10 M to 50M |
| # of Employees | 65 |
| Plant Area |
500,000
ft2
|
| Annual Production | 200,000
ton
|
| Production Hrs. Annual | 2,964
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $48,365 | 912,720 |
kWh
|
$0.053 |
| Electricity Demand | $46,994 | 4,693 |
kW-mo/yr
|
$10.01 |
| Electricity Fees | $15,352 | - |
|
- |
| Natural Gas | $670,266 | 170,724 |
MMBtu
|
$3.93 |
| Fuel Oil #2 | $3,600,000 | 126,895 |
MMBtu
|
$28.37 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $1,921,158 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $1,874,270 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #2 Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.1332: Convert combustion equipment to burn natural gas | $1,845,922 | $2,000,000 | - | - | - |
$1,845,922
-
MMBtu
|
|
| 02 | 2.2511: Insulate bare equipment | $38,483 | $20,790 | - | - |
$38,483
-
MMBtu
|
- | |
| 03 | 2.8226: Increase efficiency of trucks | $14,224 | $11,600 | - | - | - |
$14,224
-
MMBtu
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,076 | $13,090 |
$5,283
99,674
kWh
|
$2,793
-
kW-mo/yr
|
- | - | |
| 05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $5,223 | $2,520 | - | - |
$5,223
-
MMBtu
|
- | |
| 06 | 2.6127: Maintain air filters by cleaning or replacement | $2,451 | $347 |
$1,387
26,167
kWh
|
$1,064
-
kW-mo/yr
|
- | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,546 | $1,660 |
$1,167
22,024
kWh
|
$2,379
-
kW-mo/yr
|
- | - | |
| 08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,904 | $80 |
$1,756
33,140
kWh
|
$1,148
-
kW-mo/yr
|
- | - | |
| 09 | 2.2136: Install / repair insulation on steam lines | $329 | $1,104 | - | - |
$329
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $1,921,158 | $2,051,191 |
$9,593
181,005
kWh
|
$7,384
-
kW-mo/yr
|
$44,035
-
MMBtu
|
$1,860,146
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $1,874,270 | $2,016,207 |
$4,310
81,331
kWh
|
$4,591
-
kW-mo/yr
|
$5,223
-
MMBtu
|
$1,860,146
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #2 Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs