Assessment Year | 2022 |
---|---|
Principal Product | Roller Ice and Water Shields |
NAICS | 324122: Asphalt Shingle and Coating Materials Manufacturing |
SIC | 2952: Asphalt Felts and Coatings |
Sales Range | $50 M to 100M |
# of Employees | 92 |
Plant Area |
108,000
ft2
|
Annual Production | 4,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | New Hampshire |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $254,067 | 3,610,000 |
kWh
|
$0.070 | |
Electricity Demand | $178,047 | 7,296 |
kW-mo/yr
|
$24.40 | |
Electricity Fees | $4,450 | - |
|
- | |
Natural Gas | $540,399 | 52,624 |
MMBtu
|
$10.27 | |
Waste Disposal Costs | |||||
Water Usage | $60,112 | 6,859 |
Tgal
|
$8.76 | |
Water Disposal | $64,283 | 6,859 |
Tgal
|
$9.37 | |
TOTAL YEARLY COSTS | $1,101,358 | ||||
RECOMMENDED SAVINGS* | $181,356 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $7,773 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $128,459 | $1,302,718 |
$107,497
1,535,668
kWh
|
$20,962
-
kW-mo/yr
|
- | |
02 | 2.2511: Insulate bare equipment | $10,916 | $5,542 | - | - |
$10,916
-
MMBtu
|
|
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $33,534 | $15,450 |
$324
4,631
kWh
|
- |
$33,210
-
MMBtu
|
|
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,290 | $625 |
$4,265
60,935
kWh
|
$2,025
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $1,483 | $4,908 |
$824
11,773
kWh
|
$659
-
kW-mo/yr
|
- | |
06 | 2.6212: Turn off equipment during breaks, reduce operating time | $674 | $3,293 |
$454
6,490
kWh
|
$220
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $181,356 | $1,332,536 |
$113,364
1,619,497
kWh
|
$23,866
-
kW-mo/yr
|
$44,126
-
MMBtu
|
||
TOTAL IMPLEMENTED | $7,773 | $5,533 |
$5,089
72,708
kWh
|
$2,684
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs