| Assessment Year | 2020 |
|---|---|
| Principal Product | Vascular Catheters |
| NAICS | 339112: Surgical and Medical Instrument Manufacturing |
| SIC | 3841: Surgical and Medical Instruments and Apparatus |
| Sales Range | $50 M to 100M |
| # of Employees | 100 |
| Plant Area |
45,000
ft2
|
| Annual Production | 9,000,000
lb
|
| Production Hrs. Annual | 2,210
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $207,155 | 1,541,433 |
kWh
|
$0.13 | |
| Electricity Demand | $93,809 | 4,165 |
kW-mo/yr
|
$22.52 | |
| Electricity Fees | $1,080 | - |
|
- | |
| Natural Gas | $34,595 | 2,627 |
MMBtu
|
$13.17 | |
| Waste Disposal Costs | |||||
| Water Usage | $38,548 | 19,505 |
Tgal
|
$1.98 | |
| TOTAL YEARLY COSTS | $375,187 | ||||
| RECOMMENDED SAVINGS* | $119,138 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $37,160 | $156,897 |
$25,989
193,946
kWh
|
- | - | - | $11,171 | |
| 02 | 2.9114: Use solar heat to make electricty | $32,088 | $135,643 |
$22,607
167,456
kWh
|
- | - | - | $9,481 | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $31,083 | $27,315 |
$27,470
203,480
kWh
|
- | - |
$3,613
-
MMBtu
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,468 | $75,632 |
$5,782
42,832
kWh
|
$5,686
-
kW-mo/yr
|
- | - | - | |
| 05 | 2.7241: Install outside air damper / economizer on hvac unit | $3,738 | $14,935 |
$2,062
15,274
kWh
|
- | - |
$1,676
-
MMBtu
|
- | |
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,545 | $1,000 |
$2,545
18,851
kWh
|
- | - | - | - | |
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $380 | $1,000 |
$380
2,836
kWh
|
- | - | - | - | |
| 08 | 2.8121: Apply for tax-free status for energy purchases | $676 | $500 | - | - | $676 | - | - | |
| TOTAL RECOMMENDED | $119,138 | $412,922 |
$86,835
644,675
kWh
|
$5,686
-
kW-mo/yr
|
$676 |
$5,289
-
MMBtu
|
$20,652 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs