| Assessment Year | 2002 |
|---|---|
| Principal Product | Custom Injection molding |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 50 |
| Plant Area |
50,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 4,080
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $160,750 | 1,629,000 |
kWh
|
$0.099 |
| Electricity Demand | $29,532 | 5,028 |
kW-mo/yr
|
$5.87 |
| Electricity Fees | $(-2,515.0) | - |
|
- |
| Natural Gas | $14,282 | 1,445 |
MMBtu
|
$9.88 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $27,344 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $11,351 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Water Consumption Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 3.4114: Replace city water with recycled water via cooling tower | $14,262 | $23,900 |
$(-1,440.0)
(-15,218)
kWh
|
$(-407.0)
-
kW-mo/yr
|
- | - |
$16,609
-
Tgal
|
$(-500.0) | |
| 02 | 2.3212: Optimize plant power factor | $6,907 | $11,770 | - |
$6,907
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.6212: Turn off equipment during breaks, reduce operating time | $2,108 | - |
$132
1,397
kWh
|
- |
$1,976
-
MMBtu
|
- | - | - | |
| 04 | 4.821: Pay bills on time to avoid late fees | $1,510 | - | - | - | - | $1,510 | - | - | |
| 05 | 2.7224: Reduce space conditioning during non-working hours | $1,423 | $2,200 |
$858
6,446
kWh
|
- |
$565
-
MMBtu
|
- | - | - | |
| 06 | 2.7132: Install timers on light switches in little used areas | $467 | $250 |
$467
4,940
kWh
|
- | - | - | - | - | |
| 07 | 2.4133: Use most efficient type of electric motors | $359 | $230 |
$316
3,339
kWh
|
$43
-
kW-mo/yr
|
- | - | - | - | |
| 08 | 2.4314: Use synthetic lubricant | $308 | - |
$308
2,238
kWh
|
- | - | - | - | - | |
| TOTAL RECOMMENDED | $27,344 | $38,350 |
$641
3,142
kWh
|
$6,543
-
kW-mo/yr
|
$2,541
-
MMBtu
|
$1,510 |
$16,609
-
Tgal
|
$(-500.0) | ||
| TOTAL IMPLEMENTED | $11,351 | $12,250 |
$915
9,676
kWh
|
$6,950
-
kW-mo/yr
|
$1,976
-
MMBtu
|
$1,510 | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Water Consumption Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs