Assessment Year | 2024 |
---|---|
Principal Product | Industrial Valves |
NAICS | 332911: Industrial Valve Manufacturing |
SIC | 3491: Industrial Valves |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
257,240
ft2
|
Annual Production | 4,000
units
|
Production Hrs. Annual | 3,210
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $143,040 | 1,469,500 |
kWh
|
$0.097 |
Electricity Demand | $27,073 | 6,568 |
kW-mo/yr
|
$4.12 |
TOTAL YEARLY COSTS | $170,113 | |||
RECOMMENDED SAVINGS* | $22,279 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,271 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $5,988 | $275 |
$5,988
61,731
kWh
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,008 | $75 |
$1,008
10,387
kWh
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,054 | $135 |
$1,054
10,865
kWh
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,771 | $3,080 |
$3,771
38,873
kWh
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,458 | $11,138 |
$8,991
92,688
kWh
|
$1,467
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $22,279 | $14,703 |
$20,812
214,544
kWh
|
$1,467
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $21,271 | $14,628 |
$19,804
204,157
kWh
|
$1,467
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs