| Assessment Year | 2008 | 
|---|---|
| Principal Product | PVC Pipe and fittings | 
| NAICS | 326122: Plastics Pipe and Pipe Fitting Manufacturing | 
| SIC | 3084: Plastics Pipe | 
| Sales Range | $50 M  to 100M  | 
    
| # of Employees | 137 | 
| Plant Area | 
                            500,000
                 
ft2
 
                     | 
    
| Annual Production | 50,000,000
             
pieces
 
         | 
    
| Production Hrs. Annual | 8,400
             
hrs
 
         | 
    
| Location (State) | Arkansas | 
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,098,237 | 18,716,544 | 
             
kWh
 
         | 
        $0.059 | 
| Natural Gas | $100,709 | 9,080 | 
             
MMBtu
 
         | 
        $11.09 | 
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $135,128 | 
             See individual recommendations below 
            *Non-energy impacts included in savings.
         | 
    ||
| IMPLEMENTED SAVINGS* | $59,367 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | 
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $59,266 | $14,840 | 
                        $59,266
                                                     1,009,982
                                 
                                            
kWh
 
                             | 
                                                                                - | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $57,876 | $20,949 | 
                        $57,876
                                                     986,307
                                 
                                            
kWh
 
                             | 
                                                                                - | - | |
| 03 | 2.2511: Insulate bare equipment | $9,892 | $1,118 | - | 
                        $9,892
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                                                                - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,714 | $30 | 
                        $5,714
                                                     97,378
                                 
                                            
kWh
 
                             | 
                                                                                - | - | |
| 05 | 2.7224: Reduce space conditioning during non-working hours | $1,456 | $825 | 
                        $1,456
                                                     24,815
                                 
                                            
kWh
 
                             | 
                                                                                - | - | |
| 06 | 2.6211: Conserve energy by efficient use of vending machines | $823 | $1,246 | 
                        $823
                                                     14,018
                                 
                                            
kWh
 
                             | 
                                                                                - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $101 | $70 | 
                        $39
                                                     666
                                 
                                            
kWh
 
                             | 
                                                                                - | $62 | |
| TOTAL RECOMMENDED | $135,128 | $39,078 | 
                        $125,174
                                                     2,133,166
                                 
                                            
kWh
 
                             | 
                                                                                
                        $9,892
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                                                                $62 | ||
| TOTAL IMPLEMENTED | $59,367 | $14,910 | 
                        $59,305
                                                     1,010,648
                                 
                                            
kWh
 
                             | 
                                                                                - | $62 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs