Assessment Year | 2007 |
---|---|
Principal Product | Plastic food packaging |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $50 M to 100M |
# of Employees | 110 |
Plant Area |
260,000
ft2
|
Annual Production | 43,200,000
lb
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $404,726 | 14,772,786 |
kWh
|
$0.027 |
Electricity Demand | $306,527 | 24,982 |
kW-mo/yr
|
$12.27 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $43,581 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,447 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.2511: Insulate bare equipment | $23,653 | $3,315 |
$14,645
534,485
kWh
|
$9,008
-
kW-mo/yr
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $8,665 | $30 |
$5,365
195,792
kWh
|
$3,300
-
kW-mo/yr
|
- | |
03 | 2.7134: Use photocell controls | $3,379 | $360 |
$3,379
123,315
kWh
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,794 | $1,280 |
$2,349
85,727
kWh
|
$1,445
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $553 | $180 |
$553
20,180
kWh
|
- | - | |
06 | 2.6211: Conserve energy by efficient use of vending machines | $155 | $319 |
$96
3,494
kWh
|
$59
-
kW-mo/yr
|
- | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $142 | $303 |
$88
3,215
kWh
|
$54
-
kW-mo/yr
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $180 | $140 |
$36
1,327
kWh
|
$22
-
kW-mo/yr
|
$122 | |
09 | 4.611: Begin a practice of predictive / preventative maintenance | $3,060 | $2,034 | - | - | $3,060 | |
TOTAL RECOMMENDED | $43,581 | $7,961 |
$26,511
967,535
kWh
|
$13,888
-
kW-mo/yr
|
$3,182 | ||
TOTAL IMPLEMENTED | $27,447 | $4,595 |
$16,994
620,212
kWh
|
$10,453
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs