Assessment Year | 2004 |
---|---|
Principal Product | Utility connectors and poles |
NAICS | 332312: Fabricated Structural Metal Manufacturing |
SIC | 3441: Fabricated Structural Metal |
Sales Range | $10 M to 50M |
# of Employees | 135 |
Plant Area |
160,000
ft2
|
Annual Production | 25,000,000
lb
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $100,820 | 2,312,256 |
kWh
|
$0.044 |
Electricity Demand | $68,548 | 9,177 |
kW-mo/yr
|
$7.47 |
Electricity Fees | $6,515 | - |
|
- |
Natural Gas | $18,611 | 2,453 |
MMBtu
|
$7.59 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $56,708 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,563 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $29,145 | $4,275 |
$28,078
643,994
kWh
|
$1,067 | - | - | |
02 | 2.7134: Use photocell controls | $11,834 | $750 |
$11,401
281,488
kWh
|
$433 | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,732 | $4,280 |
$6,486
148,761
kWh
|
$246 | - | - | |
04 | 2.7134: Use photocell controls | $4,294 | $1,320 |
$4,137
94,878
kWh
|
$157 | - | - | |
05 | 2.3212: Optimize plant power factor | $1,111 | $3,200 | - | $1,111 | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $455 | $350 |
$145
3,329
kWh
|
$6 | $304 | - | |
07 | 2.7135: Install occupancy sensors | $225 | $240 |
$217
4,967
kWh
|
$8 | - | - | |
08 | 4.611: Begin a practice of predictive / preventative maintenance | $2,500 | $60 | - | - | - | $2,500 | |
09 | 4.611: Begin a practice of predictive / preventative maintenance | $412 | $226 | - | - | - | $412 | |
TOTAL RECOMMENDED | $56,708 | $14,701 |
$50,464
1,177,417
kWh
|
$3,028 | $304 | $2,912 | ||
TOTAL IMPLEMENTED | $27,563 | $10,426 |
$22,386
533,423
kWh
|
$1,961 | $304 | $2,912 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs