Assessment Year | 2002 |
---|---|
Principal Product | Newspapers |
NAICS |
n/a
|
SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
Sales Range | $5 M to 10M |
# of Employees | 60 |
Plant Area |
48,000
ft2
|
Annual Production | 50,000,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $151,177 | 2,971,360 |
kWh
|
$0.051 |
Electricity Demand | $36,336 | 7,267 |
kW-mo/yr
|
$5.00 |
Electricity Fees | $7,501 | - |
|
- |
Natural Gas | $2,580 | 2,617 |
MMBtu
|
$0.99 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $31,009 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,239 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $10,620 | $15,435 | - |
$10,212
-
kW-mo/yr
|
$408 | - | - | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $5,546 | - |
$4,864
95,607
kWh
|
$469
-
kW-mo/yr
|
$213 | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,800 | $1,080 |
$3,654
71,818
kWh
|
- | $146 | - | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $2,311 | - |
$2,027
39,836
kWh
|
$195
-
kW-mo/yr
|
$89 | - | - | |
05 | 2.7243: Improve air circulation with destratification fans / other methods | $2,079 | $2,307 |
$1,999
39,281
kWh
|
- | $80 | - | - | |
06 | 2.7134: Use photocell controls | $1,293 | $260 |
$1,163
22,854
kWh
|
$80
-
kW-mo/yr
|
$50 | - | - | |
07 | 4.611: Begin a practice of predictive / preventative maintenance | $1,505 | $2,255 | - | - | - | - | $1,505 | |
08 | 3.5313: Increase amount of waste recovered for resale | $3,855 | - | - | - | - |
$3,855
-
lb
|
- | |
TOTAL RECOMMENDED | $31,009 | $21,337 |
$13,707
269,396
kWh
|
$10,956
-
kW-mo/yr
|
$986 |
$3,855
-
lb
|
$1,505 | ||
TOTAL IMPLEMENTED | $11,239 | $5,642 |
$5,653
111,099
kWh
|
- | $226 |
$3,855
-
lb
|
$1,505 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs