| Assessment Year | 2001 |
|---|---|
| Principal Product | Valves |
| NAICS |
n/a
|
| SIC | 3491: Industrial Valves |
| Sales Range | $50 M to 100M |
| # of Employees | 418 |
| Plant Area |
303,000
ft2
|
| Annual Production | 410,729
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $540,319 | 12,134,270 |
kWh
|
$0.045 |
| Electricity Demand | $233,009 | 28,788 |
kW-mo/yr
|
$8.09 |
| Electricity Fees | $23,434 | - |
|
- |
| Natural Gas | $170,928 | 35,367 |
MMBtu
|
$4.83 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $138,622 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $66,499 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $53,505 | $55,889 | - |
$51,447
-
kW-mo/yr
|
$2,058 | |
| 02 | 2.7135: Install occupancy sensors | $10,056 | $297 |
$8,890
2,000,590
kWh
|
$779
-
kW-mo/yr
|
$387 | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,379 | $2,190 |
$4,211
95,018
kWh
|
- | $168 | |
| 04 | 2.3137: Use power during off-peak periods | $18,618 | - | - |
$17,902
-
kW-mo/yr
|
$716 | |
| 05 | 2.7111: Reduce illumination to minimum necessary levels | $36,180 | - |
$23,395
527,868
kWh
|
$11,393
-
kW-mo/yr
|
$1,392 | |
| 06 | 2.7224: Reduce space conditioning during non-working hours | $15,884 | $456 |
$15,273
344,613
kWh
|
- | $611 | |
| TOTAL RECOMMENDED | $138,622 | $58,832 |
$51,769
2,968,089
kWh
|
$81,521
-
kW-mo/yr
|
$5,332 | ||
| TOTAL IMPLEMENTED | $66,499 | $2,943 |
$51,769
2,968,089
kWh
|
$12,172
-
kW-mo/yr
|
$2,558 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs