| Assessment Year | 2022 |
|---|---|
| Principal Product | Molded Pulp Packaging |
| NAICS | 322299: All Other Converted Paper Product Manufacturing |
| SIC | 2679: Converted Paper and Paperboard Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 67 |
| Plant Area |
108,000
ft2
|
| Annual Production | 16,000
ton
|
| Production Hrs. Annual | 7,320
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $360,104 | 5,197,365 |
kWh
|
$0.069 | |
| Electricity Demand | $101,814 | 8,646 |
kW-mo/yr
|
$11.78 | |
| Electricity Fees | $18,039 | - |
|
- | |
| LPG | $170,848 | 9,524 |
MMBtu
|
$17.94 | |
| Other Gas | $242,853 | 122,473 |
MMBtu
|
$1.98 | |
| Waste Disposal Costs | |||||
| Water Usage | $61,778 | 115,967 |
Tgal
|
$0.53 | |
| TOTAL YEARLY COSTS | $955,436 | ||||
| RECOMMENDED SAVINGS* | $62,834 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $57,245 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7221: Lower temperature during the winter season and vice-versa | $1,109 | $12 |
$481
6,978
kWh
|
- |
$628
-
MMBtu
|
- | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $8,724 | $1,255 |
$6,819
98,825
kWh
|
$1,905
-
kW-mo/yr
|
- | - | |
| 03 | 2.4239: Eliminate or reduce compressed air usage | $634 | $152 |
$634
9,185
kWh
|
- | - | - | |
| 04 | 2.7135: Install occupancy sensors | $377 | $137 |
$377
5,470
kWh
|
- | - | - | |
| 05 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $45,478 | $37,072 | - | - |
$45,478
-
MMBtu
|
- | |
| 06 | 2.8121: Apply for tax-free status for energy purchases | $5,589 | $8,000 | - | - | - | $5,589 | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $923 | $2,186 |
$683
9,900
kWh
|
$240
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $62,834 | $48,814 |
$8,994
130,358
kWh
|
$2,145
-
kW-mo/yr
|
$46,106
-
MMBtu
|
$5,589 | ||
| TOTAL IMPLEMENTED | $57,245 | $40,814 |
$8,994
130,358
kWh
|
$2,145
-
kW-mo/yr
|
$46,106
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs