Assessment Year | 2014 |
---|---|
Principal Product | Sour Punch, Snaps, Super Ropes Brand Confections |
NAICS | 311340: Nonchocolate Confectionery Manufacturing |
SIC | 2064: Candy and Other Confectionery Products |
Sales Range | $10 M to 50M |
# of Employees | 255 |
Plant Area |
280,000
ft2
|
Annual Production | 16,000,000
pieces
|
Production Hrs. Annual | 5,736
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $300,930 | 5,168,160 |
kWh
|
$0.058 |
Electricity Demand | $135,669 | 11,286 |
kW-mo/yr
|
$12.02 |
Electricity Fees | $9,969 | - |
|
- |
Natural Gas | $122,958 | 23,002 |
MMBtu
|
$5.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $49,966 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $21,826 | - |
$21,068
361,368
kWh
|
$758
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $251 | - |
$251
4,300
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,844 | $59 |
$2,844
48,785
kWh
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $66 | $13 |
$46
792
kWh
|
$20
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $43 | $30 |
$43
743
kWh
|
- | - | |
06 | 2.7141: Lower light fixtures in high ceiling areas | $2,202 | $1,970 |
$1,538
26,386
kWh
|
$664
-
kW-mo/yr
|
- | |
07 | 2.2311: Heat treat parts only to required specifications or standards | $20,119 | $16,444 |
$(-6,128.0)
(-105,120)
kWh
|
- |
$26,247
-
MMBtu
|
|
08 | 2.4131: Size electric motors for peak operating efficiency | $2,491 | $2,716 |
$1,533
26,300
kWh
|
$958
-
kW-mo/yr
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $124 | $245 |
$87
1,486
kWh
|
$37
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $49,966 | $21,476 |
$21,282
365,040
kWh
|
$2,437
-
kW-mo/yr
|
$26,247
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs