Assessment Year | 2009 |
---|---|
Principal Product | Pharmaceutical Packager |
NAICS | 561910: Packaging and Labeling Services |
SIC | 2671: Packaging Paper and Plastics Film, Coated and Laminated |
Sales Range | $100 M to 500M |
# of Employees | 450 |
Plant Area |
275,000
ft2
|
Annual Production | 10,000,000
pieces
|
Production Hrs. Annual | 7,464
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $721,552 | 11,434,235 |
kWh
|
$0.063 |
Electricity Demand | $106,136 | 20,332 |
kW-mo/yr
|
$5.22 |
Natural Gas | $100,772 | 9,262 |
MMBtu
|
$10.88 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $61,926 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $59,227 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $338 | $525 |
$290
4,598
kWh
|
$37
-
kW-mo/yr
|
$55 | $(-44.0) | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,751 | $32,000 |
$13,362
212,097
kWh
|
$1,780
-
kW-mo/yr
|
$(-4,936.0) | $(-1,455.0) | |
03 | 2.7135: Install occupancy sensors | $7,147 | $6,214 |
$6,288
99,877
kWh
|
$859
-
kW-mo/yr
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $41,354 | $112,227 |
$22,411
355,740
kWh
|
$3,603
-
kW-mo/yr
|
$9,406 | $5,934 | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,637 | $2,750 |
$817
12,965
kWh
|
$94
-
kW-mo/yr
|
$457 | $269 | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $576 | - |
$576
9,145
kWh
|
- | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,086 | $1,265 |
$1,086
17,262
kWh
|
- | - | - | |
08 | 2.6211: Conserve energy by efficient use of vending machines | $1,037 | - |
$567
9,000
kWh
|
$470
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $61,926 | $154,981 |
$45,397
720,684
kWh
|
$6,843
-
kW-mo/yr
|
$4,982 | $4,704 | ||
TOTAL IMPLEMENTED | $59,227 | $153,716 |
$43,168
685,277
kWh
|
$6,373
-
kW-mo/yr
|
$4,982 | $4,704 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs