Assessment Year 2007
Principal Product Commercial Steering Systems
NAICS 336211: Motor Vehicle Body Manufacturing
SIC 3714: Motor Vehicle Parts and Accessories
Sales Range $100
M
to 500
M
# of Employees 325
Plant Area 260,000
ft2
Annual Production 300,000
pieces
Production Hrs. Annual 8,400
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $246,193 10,562,311
kWh
Electricity Demand $282,926 19,854
kW-mo/yr
Natural Gas $286,504 31,765
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $133,322 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $33,903

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Water Disposal Savings One-time Revenue or Avoided Cost Savings
01 2.6213: Turn off steam / hot water lines leading to space heating units $50,624 $28,500 - - - $48,415
-
MMBtu
$2,209
-
Tgal
-
02 2.5111: Convert from indirect to direct fired systems $24,453 $77,470 - - - $14,431
-
MMBtu
$10,022
-
Tgal
-
03 2.8113: Purchase gas directly from a contract gas supplier $14,325 - - - $14,325 - - -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $19,889 $167,364 $9,557
415,524
kWh
$8,222
-
kW-mo/yr
- - - $2,110
05 2.7142: Utilize higher efficiency lamps and/or ballasts $9,173 $9,173 $3,370
146,371
kWh
$4,293
-
kW-mo/yr
- - - $1,510
06 2.7142: Utilize higher efficiency lamps and/or ballasts $5,207 $3,120 $947
41,160
kWh
$841
-
kW-mo/yr
- - - $3,419
07 2.7135: Install occupancy sensors $2,672 $3,121 $2,259
98,205
kWh
$413
-
kW-mo/yr
- - - -
08 2.4133: Use most efficient type of electric motors $4,810 $4,071 $1,385
60,206
kWh
$3,425
-
kW-mo/yr
- - - -
09 2.6211: Conserve energy by efficient use of vending machines $1,787 - $248
10,800
kWh
$1,539
-
kW-mo/yr
- - - -
10 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $382 $1,026 $382
16,670
kWh
- - - - -
TOTAL RECOMMENDED $133,322 $293,845 $18,148
788,936
kWh
$18,733
-
kW-mo/yr
$14,325 $62,846
-
MMBtu
$12,231
-
Tgal
$7,039
TOTAL IMPLEMENTED $33,903 $180,684 $15,816
687,570
kWh
$14,467
-
kW-mo/yr
- - - $3,620
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Water Disposal Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs