Assessment Year | 2003 |
---|---|
Principal Product | Gears |
NAICS | 333612: Speed Changer, Industrial High-Speed Drive, and Gear Manufacturing |
SIC | 3566: Speed Changers, Industrial High-Speed Drives, and Gears |
Sales Range | $10 M to 50M |
# of Employees | 92 |
Plant Area |
130,000
ft2
|
Annual Production | 2,000
pieces
|
Production Hrs. Annual | 5,200
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $146,409 | 4,938,434 |
kWh
|
$0.030 |
Electricity Demand | $37,851 | 10,767 |
kW-mo/yr
|
$3.52 |
Electricity Fees | $156,271 | - |
|
- |
Natural Gas | $164,204 | 34,706 |
MMBtu
|
$4.73 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $78,438 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,640 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,779 | $2,600 |
$8,125
135,401
kWh
|
$654
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.6218: Turn off equipment when not in use | $3,485 | - |
$3,070
51,165
kWh
|
$415
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,567 | $29,205 |
$7,040
117,334
kWh
|
$936
-
kW-mo/yr
|
- | - | $(-436.0) | $27 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,441 | $72,201 | n/a |
$12,700
211,657
kWh
|
$2,101
-
kW-mo/yr
|
- | - | $334 | $2,306 |
05 | 2.7135: Install occupancy sensors | $1,742 | $4,527 |
$1,684
28,068
kWh
|
$58
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.1113: Reduce combustion air flow to optimum | $1,376 | - | - | - |
$1,376
-
MMBtu
|
- | - | - | |
07 | 2.2414: Use waste heat from hot flue gases to preheat | $10,728 | $19,284 | - | - |
$10,728
-
MMBtu
|
- | - | - | |
08 | 2.6218: Turn off equipment when not in use | $13,670 | - |
$13,670
227,840
kWh
|
- | - | - | - | - | |
09 | 3.7214: Reduce or eliminate waste | $13,650 | $2,107 | - | - | - |
$13,650
-
gal
|
- | - | |
TOTAL RECOMMENDED | $78,438 | $129,924 |
$46,289
771,465
kWh
|
$4,164
-
kW-mo/yr
|
$12,104
-
MMBtu
|
$13,650
-
gal
|
$(-102.0) | $2,333 | ||
TOTAL IMPLEMENTED | $13,640 | $2,600 |
$11,195
186,566
kWh
|
$1,069
-
kW-mo/yr
|
$1,376
-
MMBtu
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs