Assessment Year | 2002 |
---|---|
Principal Product | Procesed turkey products |
NAICS |
n/a
|
SIC | 2015: Poultry Slaughtering and Processing |
Sales Range | $100 M to 500M |
# of Employees | 936 |
Plant Area |
240,446
ft2
|
Annual Production | 112,500
ton
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $830,915 | 27,532,800 |
kWh
|
$0.030 |
Electricity Demand | $490,037 | 58,560 |
kW-mo/yr
|
$8.37 |
Natural Gas | $759,747 | 134,764 |
MMBtu
|
$5.64 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $129,689 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,222 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,161 | $313 |
$2,033
67,980
kWh
|
$1,128
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,061 | $20 |
$682
22,800
kWh
|
$379
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,500 | - |
$3,534
118,200
kWh
|
$1,966
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,641 | $19,029 |
$4,057
135,683
kWh
|
$2,584
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.7135: Install occupancy sensors | $380 | $532 |
$380
12,708
kWh
|
- | - | - | - | - | |
06 | 2.4133: Use most efficient type of electric motors | $6,026 | - |
$3,871
129,480
kWh
|
$2,155
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.1133: Adjust burners for efficient operation | $8,655 | $1,000 | - | - |
$8,655
-
MMBtu
|
- | - | - | |
08 | 2.1213: Direct warmest air to combustion intake | $2,260 | $2,000 | - | - |
$2,260
-
MMBtu
|
- | - | - | |
09 | 4.441: Install automatic packing equipment | $95,697 | $127,000 |
$(-2,153.0)
(-72,000)
kWh
|
$(-150.0)
-
kW-mo/yr
|
- | - | $98,000 | - | |
10 | 3.4151: Minimize water usage | $308 | $100 | - | - | - |
$305
-
Tgal
|
- |
$3
-
Tgal
|
|
TOTAL RECOMMENDED | $129,689 | $149,994 |
$12,404
414,851
kWh
|
$8,062
-
kW-mo/yr
|
$10,915
-
MMBtu
|
$305
-
Tgal
|
$98,000 |
$3
-
Tgal
|
||
TOTAL IMPLEMENTED | $4,222 | $333 |
$2,715
90,780
kWh
|
$1,507
-
kW-mo/yr
|
- | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs