| Assessment Year | 1991 |
|---|---|
| Principal Product | BRASS FITTINGS |
| NAICS |
n/a
|
| SIC | 3451: Screw Machine Products |
| Sales Range | $10 M to 50M |
| # of Employees | 180 |
| Plant Area |
n/a
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 4,794
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $396,872 | 3,208,089 |
kWh
|
$0.12 |
| Natural Gas | $24,465 | 4,275 |
MMBtu
|
$5.72 |
| Fuel Oil #2 | $40,000 | 7,000 |
MMBtu
|
$5.71 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $244,257 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $244,257 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #2 Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $631 | $1,032 |
$694
5,569
kWh
|
- | - | $(-63.0) | |
| 02 | 2.4133: Use most efficient type of electric motors | $2,973 | $742 |
$2,973
24,033
kWh
|
- | - | - | |
| 03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $5,555 | - |
$6,920
55,979
kWh
|
$(-1,365.0)
-
MMBtu
|
- | - | |
| 04 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $235,098 | - |
$237,285
1,917,937
kWh
|
- |
$40,000
-
MMBtu
|
$(-42,187.0) | |
| TOTAL RECOMMENDED | $244,257 | $1,774 |
$247,872
2,003,518
kWh
|
$(-1,365.0)
-
MMBtu
|
$40,000
-
MMBtu
|
$(-42,250.0) | ||
| TOTAL IMPLEMENTED | $244,257 | $1,774 |
$247,872
2,003,518
kWh
|
$(-1,365.0)
-
MMBtu
|
$40,000
-
MMBtu
|
$(-42,250.0) | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs