| Assessment Year | 2003 |
|---|---|
| Principal Product | COOKIES & CRACKERS |
| NAICS | 311821: Cookie and Cracker Manufacturing |
| SIC | 2052: Cookies and Crackers |
| Sales Range | $10 M to 50M |
| # of Employees | 500 |
| Plant Area |
25,000,000
ft2
|
| Annual Production | 100,000,000
lb
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $869,118 | 15,437,811 |
kWh
|
$0.056 |
| Natural Gas | $494,410 | 120,925 |
MMBtu
|
$4.09 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $257,588 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $60,575 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Consumption Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $5,286 | $450 | - |
$5,286
-
MMBtu
|
- | |
| 02 | 2.1133: Adjust burners for efficient operation | $31,370 | $5,000 | - |
$31,370
-
MMBtu
|
- | |
| 03 | 2.6218: Turn off equipment when not in use | $7,017 | - |
$7,017
51,000
kWh
|
- | - | |
| 04 | 2.7135: Install occupancy sensors | $697 | $50 |
$697
30,329
kWh
|
- | - | |
| 05 | 2.6218: Turn off equipment when not in use | $54,294 | $54,294 | n/a | - |
$30,700
-
MMBtu
|
$23,594
-
Tgal
|
| 06 | 2.1116: Improve combustion control capability | $133,000 | $622,000 | - |
$133,000
-
MMBtu
|
- | |
| 07 | 2.7132: Install timers on light switches in little used areas | $4,433 | $111 |
$4,433
73,383
kWh
|
- | - | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,580 | $12,000 |
$2,580
41,100
kWh
|
- | - | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,221 | $11,587 |
$7,221
84,373
kWh
|
- | - | |
| 10 | 2.4133: Use most efficient type of electric motors | $11,690 | $72,250 |
$11,690
236,707
kWh
|
- | - | |
| TOTAL RECOMMENDED | $257,588 | $777,742 |
$33,638
516,892
kWh
|
$200,356
-
MMBtu
|
$23,594
-
Tgal
|
||
| TOTAL IMPLEMENTED | $60,575 | $100,887 |
$29,205
443,509
kWh
|
$31,370
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Water Consumption Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs