Assessment Year | 1983 |
---|---|
Principal Product | POLYETHYLENE FILM |
NAICS |
n/a
|
SIC | 3083: Laminated Plastics Plate, Sheet, and Profile Shapes |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
n/a
|
Annual Production | 30,000,000
lb
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $629,516 | 17,507,914 |
kWh
|
$0.036 |
Natural Gas | $19,866 | 3,428 |
MMBtu
|
$5.80 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $53,382 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.3521: Reduce load on electrical conductor to reduce heating losses | $20,000 | $28,000 |
$20,000
556,858
kWh
|
- | |
02 | 2.3191: Use demand controller or load shedder | $10,422 | $9,000 |
$10,422
-
kWh
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $12,800 | $65,900 |
$12,800
357,562
kWh
|
- | |
04 | 2.3212: Optimize plant power factor | $5,360 | $12,000 |
$5,360
148,886
kWh
|
- | |
05 | 2.7243: Improve air circulation with destratification fans / other methods | $4,800 | $1,000 | - |
$4,800
-
MMBtu
|
|
TOTAL RECOMMENDED | $53,382 | $115,900 |
$48,582
1,063,306
kWh
|
$4,800
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs