Assessment Year 2026
Principal Product Surfactants
NAICS 325199: All Other Basic Organic Chemical Manufacturing
SIC 2869: Industrial Organic Chemicals, Not Elsewhere Classified
Sales Range $100
M
to 500
M
# of Employees 219
Plant Area 54,000
ft2
Annual Production 29,800
ton
Production Hrs. Annual 8,760
hrs
Location (State) Virginia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $199,675 2,395,377
kWh
Electricity Demand $17,893 4,081
kW-mo/yr
Electricity Fees $578 -
Natural Gas $30,497 3,294
MMBtu
Other Gas $716 1
MMBtu
TOTAL YEARLY COSTS $249,359
RECOMMENDED SAVINGS* $57,410 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $27,007 $22,000 $11,421
125,586
kWh
$15,586
-
MMBtu
02 2.2437: Recover waste heat from equipment $7,918 $10,000 - $7,918
-
MMBtu
03 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $12,658 $19,500 $12,658
139,098
kWh
-
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $4,007 $5,500 $4,007
44,033
kWh
-
05 2.7492: Use proper thickness of insulation on building envelope $133 $125 - $133
-
MMBtu
06 2.7142: Utilize higher efficiency lamps and/or ballasts $4,492 $4,837 $4,492
49,359
kWh
-
07 2.7234: Use heat pump for space conditioning $1,195 $14,500 $1,195
13,134
kWh
-
TOTAL RECOMMENDED $57,410 $76,462 $33,773
371,210
kWh
$23,637
-
MMBtu
TOTAL IMPLEMENTED - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs