ITAC Assessment: DL0245
ITAC logo
ITAC Assessment: DL0245
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2024
Principal Product baled wood shavings
NAICS 321999: All Other Miscellaneous Wood Product Manufacturing
SIC 2499: Wood Products, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 400
Plant Area 45,000
ft2
Annual Production 1,500,000
units
Production Hrs. Annual 4,900
hrs
Location (State) Maryland

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $184,784 1,617,289
kWh
Electricity Demand $31,751 6,517
kW-mo/yr
Electricity Fees $1,164 -
TOTAL YEARLY COSTS $217,699
RECOMMENDED SAVINGS* $33,979 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings
01 2.6212: Turn off equipment during breaks, reduce operating time $2,149 - $2,149
18,855
kWh
02 2.6212: Turn off equipment during breaks, reduce operating time $774 - $774
6,785
kWh
03 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $19,536 $53,470 $19,536
171,368
kWh
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $5,089 $9,630 $5,089
44,643
kWh
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $4,607 $6,000 $4,607
40,410
kWh
06 2.7142: Utilize higher efficiency lamps and/or ballasts $1,824 $1,592 $1,824
16,001
kWh
TOTAL RECOMMENDED $33,979 $70,692 $33,979
298,062
kWh
TOTAL IMPLEMENTED - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs