Assessment Year | 2008 |
---|---|
Principal Product | roasted coffee |
NAICS | 311920: Coffee and Tea Manufacturing |
SIC | 2095: Roasted Coffee |
Sales Range | $100 M to 500M |
# of Employees | 40 |
Plant Area |
250,000
ft2
|
Annual Production | 45,000
units
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Maryland |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $560,000 | 4,300,000 |
kWh
|
$0.13 |
Natural Gas | $500,000 | 56,000 |
MMBtu
|
$8.93 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $95,743 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $52,119 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,200 | $500 |
$5,200
47,000
kWh
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,326 | $4,000 |
$7,326
66,600
kWh
|
- | |
03 | 2.1113: Reduce combustion air flow to optimum | $44,793 | $11,000 | - |
$44,793
-
MMBtu
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $36,724 | $75,600 |
$36,724
333,855
kWh
|
- | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,700 | $3,250 |
$1,700
15,400
kWh
|
- | |
TOTAL RECOMMENDED | $95,743 | $94,350 |
$50,950
462,855
kWh
|
$44,793
-
MMBtu
|
||
TOTAL IMPLEMENTED | $52,119 | $15,000 |
$7,326
66,600
kWh
|
$44,793
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs