| Assessment Year | 2023 |
|---|---|
| Principal Product | Actuators for the oil, natural gas, mining and chemical industries |
| NAICS | 333995: Fluid Power Cylinder and Actuator Manufacturing |
| SIC | 3593: Fluid Power Cylinders and Actuators |
| Sales Range | $50 M to 100M |
| # of Employees | 150 |
| Plant Area |
540,000
ft2
|
| Annual Production | 1,000,000
units
|
| Production Hrs. Annual | 4,380
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $64,912 | 1,138,800 |
kWh
|
$0.057 | |
| Electricity Demand | $46,226 | 4,918 |
kW-mo/yr
|
$9.40 | |
| Electricity Fees | $111,137 | - |
|
- | |
| Natural Gas | $41,597 | 9,306 |
MMBtu
|
$4.47 | |
| Waste Disposal Costs | |||||
| Water Usage | $13,757 | 559,200 |
Tgal
|
$0.025 | |
| TOTAL YEARLY COSTS | $277,628 | ||||
| RECOMMENDED SAVINGS* | $63,508 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $17,675 | $20,960 |
$(-527.3)
9,250
kWh
|
- | - |
$18,202
-
MMBtu
|
- | |
| 02 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $12,461 | $15,547 | - | - | - |
$12,461
-
MMBtu
|
- | |
| 03 | 2.4322: Use or replace with energy efficient substitutes | $361 | - |
$(-145.6)
2,555
kWh
|
- | - |
$305
-
MMBtu
|
$202 | |
| 04 | 2.4133: Use most efficient type of electric motors | $19,047 | $54,963 |
$6,573
115,319
kWh
|
$12,473
-
kW-mo/yr
|
- | - | - | |
| 05 | 2.8227: Adjust / maintain fork lift trucks for most efficient operation | $10,872 | $33,000 | - | - | - | - | $10,872 | |
| 06 | 2.3137: Use power during off-peak periods | $921 | - | - | - | $921 | - | - | |
| 07 | 2.9113: Use solar heat for heat | $2,171 | $13,500 |
$2,171
38,086
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $63,508 | $137,970 |
$8,071
165,210
kWh
|
$12,473
-
kW-mo/yr
|
$921 |
$30,968
-
MMBtu
|
$11,074 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs