Assessment Year 2009
Principal Product Metal lockers
NAICS 337215: Showcase, Partition, Shelving, and Locker Manufacturing
SIC 2542: Office and Store Fixtures, Partitions, Shelving, and Lockers, Except Wood
Sales Range $10
M
to 50
M
# of Employees 130
Plant Area 110,000
ft2
Annual Production 34,000
pieces
Production Hrs. Annual 4,160
hrs
Location (State) Colorado

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $183,856 2,067,800
kWh
Electricity Demand $35,658 5,943
kW-mo/yr
Natural Gas $159,866 14,565
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $33,100 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $29,020

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Ancillary Material Cost Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $8,830 $890 $7,380
83,800
kWh
$1,450
-
kW-mo/yr
- - -
02 2.2511: Insulate bare equipment $6,050 $1,730 - - $6,050
-
MMBtu
- -
03 2.4239: Eliminate or reduce compressed air usage $1,010 $110 $840
9,500
kWh
$170
-
kW-mo/yr
- - -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $6,150 $4,590 $4,980
56,500
kWh
$980
-
kW-mo/yr
- $(-30.0) $220
05 2.7142: Utilize higher efficiency lamps and/or ballasts $4,160 $21,150 $3,410
38,700
kWh
$670
-
kW-mo/yr
- - $80
06 2.7142: Utilize higher efficiency lamps and/or ballasts $3,830 $12,240 $2,670
30,300
kWh
$750
-
kW-mo/yr
- $20 $390
07 2.7134: Use photocell controls $1,920 $210 $1,820
20,700
kWh
- - $40 $60
08 2.7135: Install occupancy sensors $1,150 $1,360 $1,080
12,300
kWh
- - $30 $40
TOTAL RECOMMENDED $33,100 $42,280 $22,180
251,800
kWh
$4,020
-
kW-mo/yr
$6,050
-
MMBtu
$60 $790
TOTAL IMPLEMENTED $29,020 $40,600 $18,440
209,300
kWh
$3,850
-
kW-mo/yr
$6,050
-
MMBtu
$(-10.0) $690
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs