Assessment Year | 2023 |
---|---|
Principal Product | PCBA and Electro-Mechanical Products |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 135 |
Plant Area |
65,000
ft2
|
Annual Production | 40,000,000
pieces
|
Production Hrs. Annual | 2,000
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $108,582 | 891,524 |
kWh
|
$0.12 |
Electricity Demand | $117,532 | 3,908 |
kW-mo/yr
|
$30.07 |
Natural Gas | $576 | 19 |
MMBtu
|
$30.16 |
TOTAL YEARLY COSTS | $226,690 | |||
RECOMMENDED SAVINGS* | $75,791 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $52,065 | - |
$52,065
427,481
kWh
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,880 | $300 |
$7,880
64,696
kWh
|
$2,000
-
kW-mo/yr
|
|
03 | 2.7493: Use double or triple glazed windows to maintain higher relative humidity and to reduce heat losses | $4,072 | $15,610 |
$4,072
33,431
kWh
|
- | |
04 | 2.7316: Centralize control of exhaust fans to ensure their shutdown, or establish program to ensure manual shutdown | $3,248 | $4,500 |
$1,431
11,750
kWh
|
$1,817
-
kW-mo/yr
|
|
05 | 2.3132: Recharge batteries on during off-peak demand periods | $2,887 | $50 | - |
$2,887
-
kW-mo/yr
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,123 | $836 |
$1,888
15,504
kWh
|
$235
-
kW-mo/yr
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $853 | - |
$636
5,221
kWh
|
$217
-
kW-mo/yr
|
|
08 | 2.6223: Schedule use of elevators to conserve energy | $663 | - |
$663
5,445
kWh
|
- | |
TOTAL RECOMMENDED | $75,791 | $21,296 |
$68,635
563,528
kWh
|
$7,156
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs