Assessment Year | 2020 |
---|---|
Principal Product | Perfumes, Cosmetics, and Toilet Preparations |
NAICS | 325611: Soap and Other Detergent Manufacturing |
SIC | 2844: Perfumes, Cosmetics, and Other Toilet Preparations |
Sales Range | less than $500 k |
# of Employees | 50 |
Plant Area |
30,100
ft2
|
Annual Production | 1,385
ton
|
Production Hrs. Annual | 5,928
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $54,721 | 1,149,000 |
kWh
|
$0.048 |
Electricity Demand | $95,550 | 4,898 |
kW-mo/yr
|
$19.51 |
Electricity Fees | $19,024 | - |
|
- |
Natural Gas | $15,839 | 5,661 |
MMBtu
|
$2.80 |
TOTAL YEARLY COSTS | $185,134 | |||
RECOMMENDED SAVINGS* | $55,478 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $37,930 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $20,215 | $200 | - | - | $20,215 | |
02 | 2.9114: Use solar heat to make electricty | $15,892 | $111,826 |
$7,208
151,427
kWh
|
$8,684
-
kW-mo/yr
|
- | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $12,108 | $6,016 |
$7,953
167,095
kWh
|
$4,155
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,979 | $1,639 |
$1,199
25,207
kWh
|
$780
-
kW-mo/yr
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,834 | $330 |
$1,027
21,580
kWh
|
$807
-
kW-mo/yr
|
- | |
06 | 2.7232: Replace existing hvac unit with high efficiency model | $1,794 | $7,400 |
$714
15,005
kWh
|
$1,080
-
kW-mo/yr
|
- | |
07 | 2.7135: Install occupancy sensors | $1,596 | $4,600 |
$1,596
33,527
kWh
|
- | - | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $60 | $281 |
$60
1,250
kWh
|
- | - | |
TOTAL RECOMMENDED | $55,478 | $132,292 |
$19,757
415,091
kWh
|
$15,506
-
kW-mo/yr
|
$20,215 | ||
TOTAL IMPLEMENTED | $37,930 | $15,585 |
$10,893
228,887
kWh
|
$6,822
-
kW-mo/yr
|
$20,215 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs