| Assessment Year | 1994 |
|---|---|
| Principal Product | wood mouldings |
| NAICS |
n/a
|
| SIC | 2431: Millwork |
| Sales Range | $5 M to 10M |
| # of Employees | 50 |
| Plant Area |
80,000
ft2
|
| Annual Production | 3,300,000
thousand feet
|
| Production Hrs. Annual | 2,600
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $115,589 | 1,105,510 |
kWh
|
$0.10 |
| Natural Gas | $11,503 | 2,715 |
MMBtu
|
$4.24 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $14,598 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $12,870 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,621 | $4,905 |
$1,621
15,533
kWh
|
|
| 02 | 2.7135: Install occupancy sensors | $107 | $150 |
$107
1,172
kWh
|
|
| 03 | 2.4133: Use most efficient type of electric motors | $6,771 | $7,024 |
$6,771
64,771
kWh
|
|
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,468 | - |
$1,468
14,068
kWh
|
|
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $870 | $700 |
$870
8,206
kWh
|
|
| 06 | 2.6212: Turn off equipment during breaks, reduce operating time | $3,761 | $2,500 |
$3,761
34,877
kWh
|
|
| TOTAL RECOMMENDED | $14,598 | $15,279 |
$14,598
138,627
kWh
|
||
| TOTAL IMPLEMENTED | $12,870 | $10,224 |
$12,870
121,922
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs