Assessment Year 2016
Principal Product Solar panels
NAICS 334413: Semiconductor and Related Device Manufacturing
SIC 3674: Semiconductors and Related Devices
Sales Range $100
M
to 500
M
# of Employees 410
Plant Area 188,180
ft2
Annual Production 569,492
pieces
Production Hrs. Annual 8,688
hrs
Location (State) Texas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,868,635 32,214,470
kWh
Electricity Demand $541,759 56,623
kW-mo/yr
Electricity Fees $183,694 -
Natural Gas $63,010 9,896
MMBtu
Waste Disposal Costs
Water Usage $429,912 48,392
Tgal
TOTAL YEARLY COSTS $3,087,010
RECOMMENDED SAVINGS* $702,519 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $74,009

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Usage Savings
01 2.7292: Lower ceiling to reduce conditioned space $566,490 $1,145,213 $464,800
7,496,490
kWh
$101,690
-
kW-mo/yr
-
02 3.4114: Replace city water with recycled water via cooling tower $53,960 - - - $53,960
-
Tgal
03 2.9113: Use solar heat for heat $31,594 $151,288 $23,818
384,167
kWh
$7,776
-
kW-mo/yr
-
04 2.7142: Utilize higher efficiency lamps and/or ballasts $24,530 $50,830 $19,570
315,705
kWh
$4,960
-
kW-mo/yr
-
05 2.4231: Reduce the pressure of compressed air to the minimum required $12,750 $50 $10,500
169,355
kWh
$2,250
-
kW-mo/yr
-
06 2.2211: Use optimum temperature $8,060 $9,230 $8,060
130,000
kWh
- -
07 2.7228: Avoid introducing hot, humid, or dirty air into hvac system $4,830 $4,560 $4,830
78,000
kWh
- -
08 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $305 - $305
4,940
kWh
- -
TOTAL RECOMMENDED $702,519 $1,361,171 $531,883
8,578,657
kWh
$116,676
-
kW-mo/yr
$53,960
-
Tgal
TOTAL IMPLEMENTED $74,009 $206,728 $59,023
952,167
kWh
$14,986
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Usage Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs