Assessment Year | 2016 |
---|---|
Principal Product | Solar panels |
NAICS | 334413: Semiconductor and Related Device Manufacturing |
SIC | 3674: Semiconductors and Related Devices |
Sales Range | $100 M to 500M |
# of Employees | 410 |
Plant Area |
188,180
ft2
|
Annual Production | 569,492
pieces
|
Production Hrs. Annual | 8,688
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,868,635 | 32,214,470 |
kWh
|
$0.058 | |
Electricity Demand | $541,759 | 56,623 |
kW-mo/yr
|
$9.57 | |
Electricity Fees | $183,694 | - |
|
- | |
Natural Gas | $63,010 | 9,896 |
MMBtu
|
$6.37 | |
Waste Disposal Costs | |||||
Water Usage | $429,912 | 48,392 |
Tgal
|
$8.88 | |
TOTAL YEARLY COSTS | $3,087,010 | ||||
RECOMMENDED SAVINGS* | $702,519 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $74,009 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Usage Savings |
---|---|---|---|---|---|---|---|
01 | 2.7292: Lower ceiling to reduce conditioned space | $566,490 | $1,145,213 |
$464,800
7,496,490
kWh
|
$101,690
-
kW-mo/yr
|
- | |
02 | 3.4114: Replace city water with recycled water via cooling tower | $53,960 | - | - | - |
$53,960
-
Tgal
|
|
03 | 2.9113: Use solar heat for heat | $31,594 | $151,288 |
$23,818
384,167
kWh
|
$7,776
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $24,530 | $50,830 |
$19,570
315,705
kWh
|
$4,960
-
kW-mo/yr
|
- | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $12,750 | $50 |
$10,500
169,355
kWh
|
$2,250
-
kW-mo/yr
|
- | |
06 | 2.2211: Use optimum temperature | $8,060 | $9,230 |
$8,060
130,000
kWh
|
- | - | |
07 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $4,830 | $4,560 |
$4,830
78,000
kWh
|
- | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $305 | - |
$305
4,940
kWh
|
- | - | |
TOTAL RECOMMENDED | $702,519 | $1,361,171 |
$531,883
8,578,657
kWh
|
$116,676
-
kW-mo/yr
|
$53,960
-
Tgal
|
||
TOTAL IMPLEMENTED | $74,009 | $206,728 |
$59,023
952,167
kWh
|
$14,986
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs