Assessment Year | 2012 |
---|---|
Principal Product | Valves |
NAICS | 335314: Relay and Industrial Control Manufacturing |
SIC | 3494: Valves and Pipe Fittings, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
140,000
ft2
|
Annual Production | 60
pieces
|
Production Hrs. Annual | 6,040
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $191,145 | 2,569,152 |
kWh
|
$0.074 |
Electricity Demand | $70,691 | 10,356 |
kW-mo/yr
|
$6.83 |
Electricity Fees | $3,935 | - |
|
- |
Natural Gas | $56,170 | 7,561 |
MMBtu
|
$7.43 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,192 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,260 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 3.3131: Use evaporation to concentrate material | $10,202 | $20,000 | - | - | - |
$(-91.0)
-
MMBtu
|
$10,293
-
Tgal
|
- | - | |
02 | 2.7124: Make a practice of turning off lights when not needed | $4,320 | $920 |
$3,520
57,600
kWh
|
$800
-
kW-mo/yr
|
- | - | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,240 | $500 |
$2,800
46,200
kWh
|
$440
-
kW-mo/yr
|
- | - | - | - | - | |
04 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $3,110 | $2,500 | - |
$3,110
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,220 | $62 |
$1,900
31,500
kWh
|
$320
-
kW-mo/yr
|
- | - | - | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,200 | $710 |
$270
4,350
kWh
|
$30
-
kW-mo/yr
|
- | - | - | $1,900 | - | |
07 | 2.8123: Pay utility bills on time | $1,700 | - | - | - | $1,700 | - | - | - | - | |
08 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $1,300 | $1,030 | - | - | - |
$1,300
-
MMBtu
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $720 | $1,900 |
$445
7,300
kWh
|
$275
-
kW-mo/yr
|
- | - | - | - | - | |
10 | 2.3512: De-energize excess transformer capacity | $180 | - | - | - | - | - | - | - | $180 | |
TOTAL RECOMMENDED | $29,192 | $27,622 |
$8,935
146,950
kWh
|
$4,975
-
kW-mo/yr
|
$1,700 |
$1,209
-
MMBtu
|
$10,293
-
Tgal
|
$1,900 | $180 | ||
TOTAL IMPLEMENTED | $9,260 | $1,420 |
$6,320
103,800
kWh
|
$1,240
-
kW-mo/yr
|
$1,700 | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs