| Assessment Year | 2008 |
|---|---|
| Principal Product | Rubber bonded products |
| NAICS | 326299: All Other Rubber Product Manufacturing |
| SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
| Sales Range | less than $500 k |
| # of Employees | 38 |
| Plant Area |
45,000
ft2
|
| Annual Production | 51,500
lb
|
| Production Hrs. Annual | 2,404
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $96,636 | 944,000 |
kWh
|
$0.10 |
| Electricity Demand | $23,244 | 4,800 |
kW-mo/yr
|
$4.84 |
| Electricity Fees | $3,000 | - |
|
- |
| Natural Gas | $41,772 | 1,842 |
MMBtu
|
$22.68 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $9,943 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,883 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $5,730 | $500 | - | - |
$5,730
-
MMBtu
|
|
| 02 | 2.7145: Install skylights | $2,160 | $4,300 |
$2,160
20,550
kWh
|
- | - | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $900 | $13 |
$710
6,750
kWh
|
$190
-
kW-mo/yr
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $595 | $275 |
$470
4,450
kWh
|
$125
-
kW-mo/yr
|
- | |
| 05 | 2.2511: Insulate bare equipment | $395 | $840 | - | - |
$395
-
MMBtu
|
|
| 06 | 2.4314: Use synthetic lubricant | $163 | - |
$130
1,265
kWh
|
$33
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $9,943 | $5,928 |
$3,470
33,015
kWh
|
$348
-
kW-mo/yr
|
$6,125
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $6,883 | $1,615 |
$600
5,715
kWh
|
$158
-
kW-mo/yr
|
$6,125
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs