| Assessment Year | 1998 |
|---|---|
| Principal Product | Architectural metal work, mostly gratings and walkways |
| NAICS |
n/a
|
| SIC | 3446: Architectural and Ornamental Metal Work |
| Sales Range | $10 M to 50M |
| # of Employees | 140 |
| Plant Area |
99,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 5,952
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $141,913 | 3,808,910 |
kWh
|
$0.037 |
| Electricity Demand | $99,270 | 16,490 |
kW-mo/yr
|
$6.02 |
| Natural Gas | $11,950 | 2,077 |
MMBtu
|
$5.75 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $61,240 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $55,790 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $28,430 | $104,000 | - |
$28,430
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 4.652: Replace existing equipment with more suitable substitutes | $21,000 | $500 | - | - | - | - | - | $21,000 | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,800 | $1,500 |
$4,800
105,510
kWh
|
- | - | - | - | - | |
| 04 | 3.8132: Use less toxic and volatile solvent substitutes | $1,840 | $3,300 | - | - |
$1,840
-
gal
|
- | - | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,630 | - |
$1,630
36,342
kWh
|
- | - | - | - | - | |
| 06 | 2.4314: Use synthetic lubricant | $1,020 | - |
$760
16,999
kWh
|
$260
-
kW-mo/yr
|
- | - | - | - | |
| 07 | 3.6192: Use a less expensive method of waste removal | $960 | - | - | - | - | - | $960 | - | |
| 08 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $820 | - |
$820
42,497
kWh
|
- | - | - | - | - | |
| 09 | 2.4133: Use most efficient type of electric motors | $590 | $1,310 |
$440
9,965
kWh
|
$150
-
kW-mo/yr
|
- | - | - | - | |
| 10 | 3.7198: Reduce / eliminate use of disposable product | $150 | $165 | - | - | - |
$150
-
lb
|
- | - | |
| TOTAL RECOMMENDED | $61,240 | $110,775 |
$8,450
211,313
kWh
|
$28,840
-
kW-mo/yr
|
$1,840
-
gal
|
$150
-
lb
|
$960 | $21,000 | ||
| TOTAL IMPLEMENTED | $55,790 | $107,475 |
$6,060
157,972
kWh
|
$28,580
-
kW-mo/yr
|
- |
$150
-
lb
|
- | $21,000 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs